BLOG

ZR-YJV Cable: Model Codes, Flame Classes, Sizes and Supplier Selection

2026/11/09

Updated 2026/11/10 · Edited by Huanghe Cable Technical Team · Reading time: 11–13 minutes

Direct Answer: Providing a comprehensive ZR-YJV Cable Specification, this guide explains that ZR-YJV cable is a widely specified Chinese industrial power cable featuring a copper conductor, cross-linked polyethylene (XLPE) insulation, and a flame-retardant PVC outer sheath. Standardly rated at 0.6/1 kV and manufactured in strict compliance with GB/T 12706.1 (adopting IEC 60502-1), it is the standard unarmoured low-voltage power distribution cable for building services, cable trays, and industrial plants. As a direct manufacturer, Huanghe Cable Group supplies full IEC 60332-3 test-verified ZR-YJV ranges from 1.5 mm² to 630 mm² for global EPC projects. The “ZR” prefix is informal shorthand; the formal flame classes under GB/T 19666 are ZA, ZB, ZC, or ZD, with ZC as the default.

ZR-YJV does not appear in the IEC 60502-1 catalogue itself, and you will not find it in a British or North American cable catalogue. If it turned up on a BOQ or a package from a Chinese contractor, that is why. Decoding the letters takes one line: ZR is flame retardant, YJ is XLPE, V is PVC sheath, and the conductor is copper unless an L appears.

What takes longer is everything those letters leave out: which flame class, which voltage, which core arrangement, and whether the sheath is actually suitable for the building it is going into. That last point is where a lot of ZR-YJV purchases go wrong, and section 6 deals with it directly.

ZR-YJV at a Glance

What it is: flame retardant, XLPE insulated, PVC sheathed copper power cable. 0.6/1 kV as standard.

Flame class: A, B, C or D under GB/T 19666, mapping to IEC 60332-3-22, 23, 24 and 25. A bare “ZR” with no class letter normally means Class C.

The trap: ZR is not LSZH. The sheath is still PVC and still releases hydrogen chloride and dense smoke when it burns.

Size range: 1.5 mm² to 630 mm² copper, 16 mm² to 630 mm² aluminium.

Cores: 1, 2, 3, 4 or 5 equal, plus 3+1, 3+2 and 4+1 reduced neutral arrangements.

Voltage: 0.6/1 kV and 1.8/3 kV in standard production. Medium voltage reviewed per project.

Standard: GB/T 12706.1, which adopts IEC 60502-1. Armoured versions add 22, 23, 32 or 33 to the code.

1. What Does ZR-YJV Stand For? Decoding the Letters

When reviewing any professional ZR-YJV Cable Specification for international B2B procurement, understanding how Chinese manufacturing designations map to IEC standards is the first step. Chinese cable designations are built from abbreviations rather than words, and each letter carries one property. Once you know the letters, any model in the family reads the same way.

ZR is the market shorthand for 阻燃 (flame retardant), but it is not a formal class under GB/T 19666. It describes a test performance, not a material. The compound is still PVC; what changes is the additive package and the oxygen index. The standard uses ZA, ZB, ZC and ZD to denote bunched flame-retardant classes. A bare “ZR” on a drawing usually means the supplier will default to Class C, because it is the easiest to pass.

One detail matters here. Since GB/T 19666 was revised, the formal notation carries a class letter: ZA, ZB, ZC or ZD. A drawing that says only “ZR-YJV” is using the older shorthand, and in practice it means Class C. If the project needs Class A or B, the drawing should say so, and section 3 explains why the difference is not cosmetic.

YJ is 交联聚乙烯, cross-linked polyethylene, abbreviated XLPE. Rated 90 °C continuous conductor temperature, 250 °C for five seconds under short circuit.

V is 聚氯乙烯, polyvinyl chloride, abbreviated PVC, used here as the sheath compound.

L after the YJ means aluminium conductor. No L means copper. The copper letter T exists in the older naming but is normally omitted.

The digits at the end describe the armour, and they follow the same convention across the whole Chinese power cable range: 22 is steel tape armour with PVC sheath, 23 is steel tape with PE sheath, 32 is steel wire with PVC sheath, 33 is steel wire with PE sheath. A model with no digits has no armour.

Then comes the specification itself, written as core count times cross-section. ZR-YJV 4×95 is four cores of 95 mm². ZR-YJV 3×240+1×120 is three main cores plus a reduced neutral.

Together, ZR-YJLV22 3×185+1×95 is a flame retardant, XLPE insulated aluminium conductor cable with steel tape armour and a PVC sheath: three 185 mm² cores plus a 95 mm² neutral. That is the whole grammar, and it is consistent across every model in the family.

Quick check: If the model code contains an L (e.g., ZR-YJLV), the conductor is aluminium. If the L is absent (e.g., ZR-YJV), the conductor is copper.

2. The Full ZR-YJV Family

The base model has no armour and is used on trays, in shafts and inside buildings. Add armour and it goes into the ground. Change the sheath and it becomes a low smoke cable with a different model code entirely.

Table 1. ZR-YJV and related models, by construction.

On mobile devices, swipe horizontally to view the complete table.

Table 1. Model designations in the ZR-YJV family
Model Conductor Armour Sheath Flame class Typical route
ZR-YJV Cu None PVC C (default) Tray, duct, indoor riser
ZR-YJV22 Cu Steel tape PVC C (default) Direct burial
ZR-YJV32 Cu Steel wire PVC C (default) Vertical shaft, steep route
ZR-YJLV Al None PVC C (default) Tray, long feeder runs
ZR-YJLV22 Al Steel tape PVC C (default) Direct burial, distribution
ZR-YJLV32 Al Steel wire PVC C (default) Vertical shaft, buried feeder
WDZ-YJY Cu None LSZH A/B/C Tunnel, metro, public building
WDZ-YJY23 Cu Steel tape LSZH A/B/C Buried, fire-critical route
WDZN-YJY Cu None LSZH A/B/C Fire pump, alarm, evacuation
ZR-VV Cu None PVC C (default) Older projects, PVC insulation

Source note: model codes follow GB/T 12706.1 and GB/T 19666. ZR-VV uses PVC insulation rather than XLPE and is listed because it still appears on older Chinese drawings.

The distinction between ZR-YJV and WDZ-YJY is the one worth understanding before you order, and it is not a marketing difference. ZR-YJV has a PVC sheath. WDZ-YJY has a low smoke zero halogen sheath, which you can find in our LSZH electric cable product line. They behave differently in a fire and they are not interchangeable, even though both carry a flame retardant claim. Section 6 goes through this in detail.

ZR-VV is on the list because it still appears on drawings from before XLPE became standard. It has PVC insulation rated 70 °C, so it carries less current for the same section and it should not be substituted for ZR-YJV without the designer agreeing.

Huanghe LV ZR-YJV, ZR-YJV22, ZR-YJV32 Cable Samples
Huanghe 0.6/1kV ZR-YJV, ZR-YJV22, ZR-YJV32 Cable Samples

3. Flame Rating A, B, C, D: What the Letter Costs

Flame retardant is not one performance level. It is four, defined by how much non-metallic material is burned in a bundle and how far the flame is allowed to travel.

GB/T 19666 sets the classes, and GB/T 18380.3 carries the test methods, which are identical in technical content to the IEC 60332-3 series. The class letter tells you the volume of combustible material per metre in the test ladder, which is a proxy for how crowded the real cable tray will be.

Table 2. Flame classes and their IEC equivalents.

On mobile devices, swipe horizontally to view the complete table.

Table 2. Flame retardant classes under GB/T 19666 and their IEC 60332-3 equivalents
Class Non-metallic volume in test IEC test method Where it is normally specified
ZA 7 L per metre IEC 60332-3-22, Category A Dense trays in tunnels, metro, high-rise risers
ZB 3.5 L per metre IEC 60332-3-23, Category B Crowded trays in plant rooms and substations
ZC 1.5 L per metre IEC 60332-3-24, Category C General building services, the usual default
ZD 0.5 L per metre IEC 60332-3-25, Category D Lightly loaded trays, single cable runs

Source note: class definitions and non-metallic volumes follow GB/T 19666. GB/T 18380.33 to .36 correspond to IEC 60332-3-22 to .25 respectively. Note that IEC 60332-3-22 (Category A) and Category A F/R are not the same test: A F/R is for cables above 35 mm² and uses a spaced ladder arrangement, so a supplier’s “Class A” report should state which category it covers. The governing edition of the project standard takes precedence.

Two practical consequences follow from this table.

A bare ZR costs less than ZA, and that is usually why you got it. Class C is the easiest to pass, so when a drawing says only ZR-YJV, a supplier will build to Class C unless someone asks. If the specification requires A or B, the price difference is real: more flame retardant additive, slower extrusion speed, and a larger test sample. On a medium-size order it can move the cable price by several percent, and it moves the delivery date too.

A single-cable flame test is not a flame class. IEC 60332-1 tests one insulated wire held vertically. It says nothing about whether a tray of twenty cables will propagate fire. Suppliers sometimes present a 60332-1 report as evidence of flame retardancy, and it is not the same claim. If the project needs a class, ask for the 60332-3 report at the matching category.

There is also a design question underneath the class. Flame retardant cable stops the fire from spreading along the tray. It does not survive a fire, and it does not protect circuits that have to keep working during one. That is a fire resistant cable, which is a different model (WDZN-YJY and similar), tested under a different standard. Projects sometimes specify ZR when they meant fire resistant, and the mistake only becomes visible at commissioning.

Not sure which flame class your drawing actually requires?

If the BOQ says only “ZR-YJV”, send us the project type and cable tray density. We will tell you what class the installation needs, and quote both C and A so you can compare.

4. Core Arrangements, Cross-Sections and Current Ratings for ZR-YJV Copper Cables

A ZR-YJV order needs three numbers that are often left vague on enquiries: how many cores, whether the cores are equal, and what cross-section. Each of them changes the price, and the core arrangement changes it the most.

Equal cores are the simple case. Four equal cores carry three phases plus a protective earth. Five equal cores add a neutral. Reduced arrangements exist because a neutral or an earth rarely carries the same current as a phase, so building it smaller saves copper without affecting the circuit.

Table 3. Core arrangements and their cost effect.

On mobile devices, swipe horizontally to view the complete table.

Table 3. Core arrangements for ZR-YJV and their relative cost
Notation Meaning Relative cost Typical use
1×S Single core Lowest per metre Feeder, duct, DC link
2×S Two equal cores Low Single phase, small loads
3×S Three equal cores Baseline Three phase, earth elsewhere
4×S Four equal cores About 30% above 3×S Three phase plus PE
5×S Five equal cores Highest Three phase plus N plus PE
3×S+1×S/2 Three main plus reduced PE 10 to 15% below 4×S Motors, feeders with separate earth
3×S+2×S/2 Three main plus reduced N and PE 15 to 20% below 5×S Distribution with light neutral
4×S+1×S/2 Four main plus reduced PE About 10% below 5×S Three phase plus full N

Source note: relative cost figures reflect typical copper content differences and exclude armour and sheath. The reduced neutral is not permitted where harmonic currents are significant; check the design before substituting.

On cross-section, ZR-YJV runs from 1.5 mm² to 630 mm² in copper and from 16 mm² to 630 mm² in aluminium. Aluminium starts higher because small aluminium conductors are fragile at terminations and the current rating per unit area is lower.

Current ratings below are for copper conductors, XLPE insulation, 0.6/1 kV, and three loaded conductors, at an ambient air temperature of 30 °C in free air and a soil temperature of 20 °C (thermal resistivity 2.5 K·m/W) for buried installations. These baselines align with IEC 60364-5-52. The values are indicative, and derating for grouping, depth, soil thermal resistivity, and altitude must be applied on top for the final design.

Table 4. Indicative current rating, copper ZR-YJV, 0.6/1 kV.

On mobile devices, swipe horizontally to view the complete table.

Table 4. Indicative current ratings for copper ZR-YJV, 0.6/1 kV, three loaded conductors
Cross-section (mm²) Free air, tray (A) Buried in duct (A) Typical application
1.5 22 22 Control, lighting final circuit
2.5 30 29 Socket circuits, small equipment
4 40 38 Small motor branch
6 51 47 Sub-main, small feeder
10 70 63 Distribution board feed
16 94 81 Panel feeder, HVAC
25 119 104 Main distribution branch
35 147 125 Sub-main in plant
50 179 148 Building sub-main
70 229 183 Main feeder
95 278 216 Transformer to board
120 322 246 Main feeder
150 371 278 Main feeder, riser
185 424 312 Main feeder, riser
240 500 361 Incoming feeder
300 576 408 Incoming feeder
400 656 469 Transformer connection
500 749 533 Main incoming
630 855 600 Main incoming, large plant

Source note: Indicative values derived from the order of magnitude of IEC 60364-5-52 for a single circuit in free air or buried in duct. Engineering caveat for large sizes (300 mm² to 630 mm²): When multiple multi-core cables are bunched on trays or share a duct, skin effect, proximity effect, and mutual heating drastically reduce current-carrying capacity. The values above assume an isolated circuit; always apply the grouping derating factors from the project’s installation standard before final cable sizing.

Huanghe Cables Production Workshop

5. Voltage Grades and Where ZR-YJV Stops

A ZR-YJV order without a voltage grade is assumed to be 0.6/1 kV. That assumption is right most of the time, and it is wrong often enough to be worth writing the voltage on the enquiry.

The Chinese low-voltage power cable range covers two grades under GB/T 12706.1: 0.6/1 kV and 1.8/3 kV. The second is used for heavy equipment, mining and large motor circuits where the voltage drop over a long run makes the higher grade worthwhile.

Table 5. Voltage grades and how the model code changes.

On mobile devices, swipe horizontally to view the complete table.

Table 5. Voltage grades for XLPE insulated power cable
U0/U Um Standard Model notation Where used
0.6/1 kV 1.2 kV GB/T 12706.1, IEC 60502-1 ZR-YJV Building services, LV distribution
1.8/3 kV 3.6 kV GB/T 12706.1, IEC 60502-1 ZR-YJV-1.8/3 Mining, heavy motors, long runs
3.6/6 kV 7.2 kV GB/T 12706.2, IEC 60502-2 ZR-YJV-3.6/6 MV distribution
6/10 kV 12 kV GB/T 12706.2, IEC 60502-2 ZR-YJV-6/10 MV distribution, industrial
8.7/15 kV 17.5 kV GB/T 12706.2, IEC 60502-2 ZR-YJV-8.7/15 MV feeder, substation
12/20 kV 24 kV GB/T 12706.2, IEC 60502-2 ZR-YJV-12/20 MV feeder
18/30 kV 36 kV GB/T 12706.2, IEC 60502-2 ZR-YJV-18/30 MV feeder, utility
26/35 kV 40.5 kV GB/T 12706.3, IEC 60502-2 ZR-YJV-26/35 Utility distribution

Source note: voltage designations follow GB/T 12706 and IEC 60502. U0 is the phase-to-earth voltage and U the phase-to-phase voltage; Um is the maximum system voltage.

It is vital to separate 1.8/3 kV from the screened medium-voltage range (3.6/6 kV and above). While 1.8/3 kV sits at the very bottom of the MV band under IEC definitions, its physical construction uses the same unscreened extrusion principle as 0.6/1 kV—just with a thicker XLPE wall. It does not carry conductor or insulation screens.

Two things change fundamentally once you cross into 3.6/6 kV and above:

  • The construction changes: True MV XLPE cable requires a triple-extrusion layer (conductor screen, XLPE insulation, insulation screen), followed by a metallic electrostatic screen (copper tape or copper wire).
  • The accessories change: MV cables require stress-controlled terminations and joints installed by certified technicians.

If your enquiry is for medium voltage, say so at the top. It routes to a different production line and a different quotation structure.

Huanghe 0.6/1 kV ZR-YJV Cable Production Line
Huanghe 0.6/1 kV ZR-YJV Cable Production Line

6. ZR Is Not LSZH, and the Difference Is a Rejected Shipment

This is the most expensive misunderstanding in the whole ZR-YJV category, and it happens on real projects.

A specification says the cable must be flame retardant and low smoke. The buyer reads ZR as covering both, orders ZR-YJV, and receives a cable with a PVC sheath. It passes the flame test. It fails everything else the project asked for, because burning PVC produces hydrogen chloride and dense black smoke, which is exactly what a tunnel or a metro station cannot have.

Flame retardant and low smoke zero halogen are two different properties, measured by two different test series, and only one of them is in the ZR prefix.

Table 6. ZR-YJV against WDZ-YJY, the low smoke alternative.

On mobile devices, swipe horizontally to view the complete table.

Table 6. ZR-YJV and WDZ-YJY compared on fire performance
Property ZR-YJV WDZ-YJY Test reference
Sheath compound PVC with flame retardant additives Halogen free polyolefin GB/T 12706.1 compound requirements
Combustion products Hydrogen chloride, carbon monoxide, dense smoke Mainly water vapour and carbon dioxide IEC 60754-1 and -2
Halogen acid gas Significant, acidic, corrosive to electronics Below the threshold, conductivity and pH both pass IEC 60754-1, IEC 60754-2
Smoke density High, light transmission falls quickly Low, light transmission typically above 60% IEC 61034-2
Flame propagation Class A, B, C or D Class A, B or C IEC 60332-3-22 to -25
Relative price Baseline 15 to 30% higher, more on small sizes Compound cost and slower extrusion
Where it belongs General buildings, outdoor, plant rooms Tunnel, metro, data hall, public assembly Occupancy and evacuation risk

Source note: fire test references follow IEC 60332-3, IEC 60754 and IEC 61034, which GB/T 18380, GB/T 17650 and GB/T 17651 adopt. Relative price reflects typical production cost differences and varies with size and sheath share of the total.

The practical rule is short. If the building has people who cannot evacuate quickly, or equipment that cannot be replaced quickly, the sheath needs to be halogen free. That means WDZ-YJY or WDZ-YJY23, not ZR-YJV, regardless of what the flame class says.

The price gap is why this goes wrong. LSZH compound costs more and extrudes slower, so a supplier quoting against a ZR-YJV line is quoting a cheaper cable. If the quotation came back noticeably below the others and the model says ZR-YJV while the specification said low smoke, that is the reason.

Not Sure Whether You Need ZR-YJV or WDZ-YJY?

Send Huanghe the occupancy type, the route and the specification clause. We will tell you which sheath the project actually requires, and quote both so you can see the difference.

7. ZR-YJV Cable Specification Equivalents: What It Is Called in IEC, BS and North American Markets

There is no IEC model designation for ZR-YJV, because IEC 60502-1 defines constructions and test requirements rather than product names. Every market translates it differently, and some markets have no exact equivalent at all.

Table 7. ZR-YJV against British and North American equivalents.

On mobile devices, swipe horizontally to view the complete table.

Table 7. ZR-YJV models translated into British and North American descriptions
Chinese model IEC construction description British equivalent North American analogue
ZR-YJV Cu/XLPE/PVC, flame retardant, 0.6/1 kV, unarmoured Conforms to IEC 60502-1. In UK practice, unarmoured XLPE/PVC industrial power cables are typically specified directly to IEC standards rather than BS 5467, which governs armoured (SWA) types. Single core XHHW-2; multicore tray cable to UL 1277 where permitted
ZR-YJV22 Cu/XLPE/STA/PVC, 0.6/1 kV BS 5467 permits steel tape armour at this voltage No direct equivalent; US practice favours conduit or tray cable
ZR-YJV32 Cu/XLPE/SWA/PVC, 0.6/1 kV BS 5467 steel wire armour, the closest match in the British range No direct equivalent
WDZ-YJY Cu/XLPE/LSZH, 0.6/1 kV BS 6724 construction, low smoke zero halogen LSZH tray cable where the specification permits
ZR-YJLV Al/XLPE/PVC, flame retardant, 0.6/1 kV Aluminium conductor is not a standard option in the BS 5467 range Aluminium XHHW-2 is common in US distribution

Source note: equivalences are descriptive, not certified substitutions. A design that specifies a British or North American product standard requires that standard to be met, and the substitution should be confirmed in writing by the designer.

The point of this table is not to encourage substitution. It is to let you read a Chinese drawing and a local specification side by side, so you can tell whether they describe the same cable or two different ones.

One pattern is worth noting. British practice puts armour on almost everything at 0.6/1 kV, because a great deal of it goes into the ground. Chinese practice uses unarmoured cable far more, because a great deal of it goes onto trays inside buildings. When a Chinese-designed project is built in a market with British-derived standards, the cable schedule often contains unarmoured models where the local reviewer expects armour. That is a design conversation, and it is better to have it before the order than after the delivery.

Huanghe Cable factory cable testing equipment
Factory testing equipment. The applicable inspection record and test scope should be confirmed for each order.

8. Huanghe: Range, Standards and What We Hold

Huanghe Cable manufactures low-voltage power cable in China and exports to South America, Southeast Asia, Central Asia and Africa. ZR-YJV is one of the models we build continuously, not a special request.

What matters for a buyer is that the process steps deciding whether a flame retardant cable performs are all done in-house: conductor stranding, XLPE extrusion and cross-linking, and sheath extrusion with the flame retardant compound. When the sheath is bought in from a compounder and extruded on someone else’s line, the flame class on the certificate and the flame class in the drum can drift apart.

What we build in this family.

Models: ZR-YJV, ZR-YJV22, ZR-YJV32, ZR-YJLV, ZR-YJLV22, ZR-YJLV32, and the WDZ-YJY and WDZ-YJY23 low smoke versions.

Cross-section: 1.5 mm² to 630 mm² copper, 16 mm² to 630 mm² aluminium.

Cores: 1, 2, 3, 4 and 5 equal, plus 3+1, 3+2 and 4+1 reduced arrangements.

Flame class: Class A, B and C to GB/T 19666, with the matching IEC 60332-3 test evidence.

Voltage: 0.6/1 kV and 1.8/3 kV in standard production. Medium voltage reviewed per project.

Standards: GB/T 12706.1 and IEC 60502-1. Constructions to BS 5467 and BS 6724 are also built.

What we hold. IEC test evidence for the constructions we build: conductor resistance, voltage withstand and insulation resistance per drum, plus flame propagation to IEC 60332-3 at the specified category, halogen acid gas to IEC 60754, and smoke density to IEC 61034 for the low smoke models.

What we do not hold. We do not hold BASEC or LPCB product certification, nor do we provide an EN 50575 CPR (Construction Products Regulation) classification. Because CE-marked CPR compliance is mandatory for permanent buildings within the European Union, our standard ZR-YJV line is not supplied for EU building projects requiring formal CPR Euroclasses. If your project is outside the EU (such as in Southeast Asia, Africa, or South America) where IEC standards apply directly, our IEC 60332-3 test reports provide full verification.

That distinction matters more in this product family than in most, because flame retardant performance is exactly the kind of claim that buyers cannot verify by looking at a drum. If a specification requires a third-party product certificate rather than a construction built and tested to a standard, tell us at enquiry stage. We will say plainly that we cannot supply it, and the enquiry can end there rather than at the port.

A note on flame class claims. “Flame retardant” on its own means very little, because it does not say which class. Ask for the class letter and the IEC 60332-3 category on the test report. A supplier who cannot state the category is either working to Class C by default or has not tested, and both are worth knowing before you place the order.

Huanghe Cable manufacturing and export experience in ZR-YJV cables
Huanghe ZR-YJV cables supplied for projects in markets including Laos, Mongolia, South Africa and Azerbaijan

9. MOQ, Lead Time and Container Loading

ZR-YJV is lighter than the armoured equivalent, so container loading is more generous. The production constraints are different, though, and they are what usually decides the delivery date.

MOQ. It applies per size, because each size is a separate extrusion and stranding run. A schedule with eight sizes is eight runs. Small quantities of large sizes are the combination that decides whether an order is workable, so flag them early.

Lead time. Three things move it. Flame class matters: Class A needs more additive and a slower line speed than Class C. Sheath material matters: LSZH runs slower than PVC because the compound is more sensitive to process temperature. Armour matters: a ZR-YJV32 takes longer than a ZR-YJV at the same conductor size, because wire drawing and armouring are extra steps.

Ask for the lead time in writing, separately for standard season and peak season. One number quoted in a quiet month is not a commitment.

Table 8. Approximate container loading for ZR-YJV copper cable.

On mobile devices, swipe horizontally to view the complete table.

Table 8. Indicative container loading, ZR-YJV copper cable, 0.6/1 kV
Size (mm²) Mass (kg/m) Approx. metres, 20GP Approx. metres, 40HQ Limiting factor
25 1.55 About 11,600 m About 16,100 m Volume, then payload
50 2.75 About 6,500 m About 9,000 m Payload
95 4.60 About 3,900 m About 5,400 m Payload
150 6.80 About 2,600 m About 3,600 m Payload
240 10.7 About 1,680 m About 2,300 m Payload and drum diameter
400 17.4 About 1,030 m About 1,430 m Payload and drum diameter
630 27.2 About 660 m About 900 m Drum diameter first, then payload

Source note: indicative only, based on a 20GP payload of about 18 t and a 40HQ payload of about 25 t with typical drum sizes for unarmoured cable. Actual loading depends on drum diameter, drum count, port weight limits and road limits at destination. Confirm the drum plan before booking.

Two logistics details that cause problems after the order is placed.

Drum diameter at 400 and 630 mm². The drum becomes the constraint before the weight does. A drum that does not fit a standard flatbed, or that exceeds a destination road limit, turns into a re-packing job at the port. Agree the drum diameter in writing.

Destination axle limits. Some markets restrict axle load on the final road leg. A 40HQ at full payload may need two trucks, which changes the delivered cost. If your site is inland, say so at quotation stage.

10. The RFQ That Gets a Usable Quotation

An enquiry that reads “ZR-YJV 4×95, 500 m” produces quotations that cannot be compared, because the flame class, the voltage, the neutral arrangement and the drum length are all still open. Each of them moves the price.

Checklist: what to include in the enquiry

Model: ZR-YJV, ZR-YJV22, ZR-YJV32, or the low smoke WDZ equivalent.

Flame class: A, B or C. If the drawing says only ZR, say so and we will quote Class C as the default and flag it.

Voltage: 0.6/1 kV or 1.8/3 kV. Medium voltage needs its own grade.

Conductor: copper or aluminium.

Core arrangement: equal, or the reduced notation.

Size list: every size on the BOQ with quantity per size.

Route: tray, duct, buried, or riser. This decides whether armour is needed at all.

Drum length: preferred length, and whether split drums are acceptable.

Delivery: destination port, Incoterm, target schedule.

Price basis: reference date for copper, and the validity you need.

Documents: routine test certificates per drum, IEC 60332-3 report at the specified category, and whether third-party inspection is required.

Example enquiry, written so it can be answered

Model: ZR-YJV, flame class C

Voltage: 0.6/1 kV

Sizes: 4×95 mm², 620 m; 4×50 mm², 480 m; 3×240+1×120 mm², 300 m

Conductor: copper, Class 2 compacted

Route: cable tray in a plant room, 180 m buried direct in the yard section

Drum: 500 m preferred, split drums acceptable

Delivery: CIF Mombasa, copper basis LME cash settlement on order date, validity 7 days

Documents: routine test certificate per drum, IEC 60332-3-24 report, third-party inspection acceptable

That enquiry can be answered line by line, and two quotations built from it can be compared. The one above also exposes a decision: the route includes a buried section, so the 4×95 and 4×50 may need ZR-YJV22 rather than ZR-YJV. A supplier reading the route carefully will say so. A supplier quoting the model string alone will not.

Need a Printable Spec Sheet for Your Submittal?

If you are compiling a technical submittal for an engineering consultant or preparing a BOQ, copying tables from a webpage is inefficient. Send us your BOQ for a verified compliance review, or request a PDF datasheet for the exact construction.

11. Frequently Asked Questions

What does ZR-YJV stand for?

ZR is flame retardant, YJ is XLPE insulation, V is PVC sheath, and the conductor is copper. A bare ZR-YJV without a class letter is normally built to flame class C. If the project needs Class A or B, the class has to be written into the specification, because the price and the test report both change.

Is ZR-YJV the same as LSZH cable?

No, and this is the most common mistake in the category. ZR-YJV has a PVC sheath, which releases hydrogen chloride and dense smoke when it burns. A low smoke zero halogen cable is WDZ-YJY or WDZ-YJY23, with a halogen free sheath tested to IEC 60754 and IEC 61034. Both can carry a flame class, but only one is suitable for tunnels, metro and crowded public buildings.

What flame classes are available, and what do they mean?

Four: ZA, ZB, ZC and ZD under GB/T 19666, corresponding to IEC 60332-3-22, -23, -24 and -25. The class defines how much non-metallic material is burned in the test, from 7 L per metre for Class A down to 0.5 L per metre for Class D. A higher class means a denser cable tray can be protected, and it costs more because it needs more additive and slower production.

What sizes and core arrangements do you manufacture?

1.5 mm² to 630 mm² per conductor in copper, 16 mm² to 630 mm² in aluminium. One to five equal cores, plus 3+1, 3+2 and 4+1 reduced arrangements. Above 300 mm² the drum diameter becomes the practical constraint, so the drum plan should be agreed before the order.

What voltage grades are available?

0.6/1 kV and 1.8/3 kV are standard production. Medium voltage from 3.6/6 kV up to 26/35 kV is reviewed per project, because the construction changes: screened cores, larger diameter, different termination kits. A medium voltage enquiry should state the U0/U grade at the top.

Do you make armoured versions of ZR-YJV?

Yes. ZR-YJV22 is steel tape armour with PVC sheath, ZR-YJV32 is steel wire armour with PVC sheath, and the aluminium equivalents are ZR-YJLV22 and ZR-YJLV32. If the route includes a buried section, armour is normally required, and it is worth checking whether the drawing says so.

Can you build to IEC 60502-1 and to British Standard constructions?

Yes. GB/T 12706.1 adopts IEC 60502-1, so the two are aligned in technical content. Constructions to BS 5467 and BS 6724 are also built. We do not hold BASEC or LPCB product certification and we do not hold a CPR classification under EN 50575, so if the specification requires a product certificate rather than a construction built to the standard, tell us before we quote.

What test evidence can you provide?

Routine tests per drum covering conductor resistance, voltage withstand and insulation resistance. For flame performance, an IEC 60332-3 report at the category matching the class ordered. For low smoke models, IEC 60754 and IEC 61034 reports. A single-cable test to IEC 60332-1 is not a flame class and we do not present it as one.

What is your MOQ and lead time?

MOQ applies per size, because each size is a separate production run. Lead time depends on the flame class, the sheath material and whether armour is required: Class A is slower than Class C, LSZH is slower than PVC, and an armoured model is slower than an unarmoured one at the same conductor size. Ask for the figure in writing, separately for standard and peak season.

How is the price calculated?

On the metal content at a stated basis date, plus the flame class, the construction, the drum length and the freight term. Copper can move several percent in a month, so ask for the basis date and the validity period. A price without a basis is not a firm price.

How many metres fit in a container?

For copper ZR-YJV, roughly 5,400 m of 4×95 mm² in a 40HQ, about 3,600 m of 4×150 mm², and about 900 m of 4×630 mm². Unarmoured cable loads more metres than the armoured equivalent. These are weight and drum limited estimates; actual loading depends on drum diameter and destination road limits.

Do you accept third-party inspection?

Yes. SGS, BV, TÜV, Intertek or a nominated inspector, with the scope agreed before the visit and access to the test bay. We prefer the scope to be fixed at order stage, because inspection requirements added later usually arrive after the drum has been packed.

Related Reading

Sources and scope: Model designations and construction requirements follow GB/T 12706.1, GB/T 12706.2 and IEC 60502-1. Flame classes follow GB/T 19666, with test methods in GB/T 18380.3 corresponding to IEC 60332-3. Halogen and smoke test references follow IEC 60754 and IEC 61034. Current ratings are indicative and in the order of magnitude of IEC 60364-5-52; the edition in force for the project governs. Published November 2026.

Technical note: Cable selection, protective device coordination, fire strategy and earthing design remain the responsibility of the project engineer. The information on this page supports procurement decisions and does not replace the installation design.

Leave a Message

Please contact us for a free quotation by the below form. We promise the quickest response within 12 hours.

    Home Whatsapp Mail Inquiry